Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 27, 2020, 11:18 AM
  • A 0307_A 0306 _02272020_032340.mp4

Date
02/27/2020
W/O
URGENT
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00325
PipeID
P08217
Time
3:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7421
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
URGENT_FEB_2020_A
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
A 0306
Downstream MH
A 0307
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole A 0306 to A 0307
MH: A 0306MH: A 0307upstream0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES2 ft. MWL - Water Level, 100 %of cross sectional area2 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - A 0306

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWL
2SAP
0MWM
2SSS
2MSAVIEW OF UPLEG OF D/S SIPHON.
2DAGS
0AMHA 0306

Properties (7)

additional_info
SC398810
custom_field_two
5
customer
LACSD
datetime
2020-02-27T03:18:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
28972