- Date
- 02/27/2020
- W/O
- URGENT
- Weather
- Dry
- Operator/Surveyor
- S.LOPEZ
- Sewer ID
- Z00325
- PipeID
- P08217
- Time
- 2:28 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7421
- Sewer Name
- A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
- City
- EL MONTE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 29
- Purpose
- Routine Assessment
- Project
- URGENT_FEB_2020_A
- Sewer Type
- Siphon
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 63 in.
- Width
- 63 in.
- Upstream MH
- A 0307
- Downstream MH
- A 0306
- Dir. of Survey
- Downstream
- Length Surveyed
- 205 ft.
- Total Length
- 205 ft.
- Structural Index
- 2
- Structural Quick
- 3E2F
- Structural Rating
- 163
- O&M Index
- 2
- O&M Quick
- 412O
- O&M Rating
- 166
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 329
Pipe schematic from manhole A 0307 to A 0306 Observation photos (6)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

27.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

48.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

160.4 ft. - General Photograph - PROJECTING AGGREGATE

169.5 ft. - General Photograph - PROJECTING AGGREGATE

205 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.