Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 13, 2020, 06:52 AM
  • 32 1079_32 1078_02122020_231459.mp4

Date
02/12/2020
W/O
808150
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19528
Time
10:52 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7406
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_808150_TV32058_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1079
Downstream MH
32 1078
Dir. of Survey
Downstream
Length Surveyed
270.2 ft.
Total Length
270.2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
4131
O&M Rating
113
Overall Index
2
Overall Quick
Overall Rating
118
Pipe schematic from manhole 32 1079 to 32 1078
MH: 32 1079MH: 32 1078downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10790 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"37.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES63.5 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"69.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"124 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"134.3 ft. CS - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES142.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"215.8 ft. TBI - Tap Break-In Intruding, at 03 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"240 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"268.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish270.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1078270.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    37.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

    134.3 ft. - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In Intruding, at 03 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

    215.8 ft. - Tap Break-In Intruding, at 03 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

Observations (18)

DistanceCodeObservation
0MWM
69.2TFA
268.5DAGS
270.2AMH32 1078
215.8TBI
0AMH32 1079
179.2TBA
0MWL
63.5TBA
134.3CS
124TBA
8.2TFC
37.3FL
240TFA
2DAGS
142.1TBA
0MGOCONNECTION AT MH 3 O'CLOCK
270.2MGOCONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC398795
custom_field_two
2
customer
LACSD
datetime
2020-02-12T22:52:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false