- Date
- 02/12/2020
- W/O
- 808150
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00841
- PipeID
- P19520
- Time
- 11:56 PM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7406
- Sewer Name
- 32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
- City
- SANTA CLARITA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 32
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- RFIR_WO_808150_TV32058_JAN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 32 1072
- Downstream MH
- 32 1071
- Dir. of Survey
- Downstream
- Length Surveyed
- 150.1 ft.
- Total Length
- 150.1 ft.
- Structural Index
- 4
- Structural Quick
- 4131
- Structural Rating
- 7
- O&M Index
- 2
- O&M Quick
- 2E12
- O&M Rating
- 60
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 67
Pipe schematic from manhole 32 1072 to 32 1071 Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

5.7 ft. - Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

100.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

101.5 ft. - Roots Fine Connection, from 10 to 02 o'clock, within 8 inches of joint: YES

104.1 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES