Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2020, 05:44 PM
  • A 0588_A 0587 _01242020_100627.mp4

Date
01/24/2020
W/O
803059
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00316
PipeID
P07793
Time
9:44 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7305
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_803059_TV21041_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
A 0588
Downstream MH
A 0587
Dir. of Survey
Downstream
Length Surveyed
419.8 ft.
Total Length
419.8 ft.
Structural Index
4
Structural Quick
5O3O
Structural Rating
640
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
640
Pipe schematic from manhole A 0588 to A 0587
MH: A 0588MH: A 0587downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05880 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FROM PREVIOUS INSPECTIONS2 ft. MGO - General Observation - MAG COAT THROUGHOUT START2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start404 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish404 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish404.5 ft. MGO - General Observation - MAG COAT THROUGHOUT END419.8 ft. AMH - Downstream Manhole, Survey Ends - A 0587

Observations (10)

DistanceCodeObservation
404SAP
404.5MGOMAG COAT THROUGHOUT END
0MWL
419.8AMHA 0587
2SRVFROM PREVIOUS INSPECTIONS
2MGOMAG COAT THROUGHOUT START
404SRV
0AMHA 0588
2SAP
0MWM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2020-01-24T09:44:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false