Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2016, 09:53 AM
  • 08 0306_08 0305A_1032016_025806.mp4

Date
10/03/2016
W/O
0591702
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00013
PipeID
P00355
Time
2:53 AM
Certificate
101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0304
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20160930MDM_KEYSTONE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0306
Downstream MH
08 0305A
Dir. of Survey
Downstream
Length Surveyed
94.5 ft.
Total Length
94.5 ft.
Structural Index
2
Structural Quick
352A
Structural Rating
35
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
35
Pipe schematic from manhole 08 0306 to 08 0305A
MH: 08 0306MH: 08 0305Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active5.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE11.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H11.2 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H14.1 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H17.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H32.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - S32.4 ft. MWM - Water Mark, 30 %of cross sectional area39.3 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H41.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H50.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped55.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H59 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H62 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H71.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H77 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H79.3 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - H79.3 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - H82.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H86.1 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H94 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active94.5 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (2)

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

    11.2 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H

    14.1 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H

Observations (25)

DistanceCodeObservation
11.2FCH
94.5AMH3:20AM
0MWL
39.3FCH
32.4FCS
94MGOConn. @ Mh, 9 O' Clock. Active
41.2FCH
79.3FSH
86.1FCH
79.3FSH
71.2FCH
62FLH
50.3TFCCapped
14.1FSH
55.8FLH
0MWM
82.9FCH
0AMH2:55AM
59FLH
0MGOConn. @ Mh, 3 O' Clock. Active
11.2FSH
17.3FCH
77FCH
5.1FCHAIRLINE
32.4MWM

Properties (6)

custom_field_three
HAIRLINE SPIRAL FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-10-03T02:53:25-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false