Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2016, 10:40 AM
  • 08 0310_08 0309_9302016_035843.mp4

Date
09/30/2016
W/O
0591702
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00013
PipeID
P00357
Time
3:40 AM
Certificate
101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0301
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20160930MDM_KEYSTONE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0310
Downstream MH
08 0309
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
2
Structural Quick
362D
Structural Rating
64
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 08 0310 to 08 0309
MH: 08 0310MH: 08 0309downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:55AM0 ft. MWM - Water Mark, 30 %of cross sectional area12.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE13.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H15.5 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - H15.5 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - H38.2 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H38.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped74.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active82.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H82.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H85.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H85.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H87.8 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H115.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H122.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped130.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H141.7 ft. MGO - General Observation - 15" VCP151.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - S151.5 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish - H151.5 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT151.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H151.5 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT157.6 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - H157.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H160.4 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - S172.7 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - S179 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped205.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - S221 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - S226.7 ft. MGP - General Photograph226.7 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES227 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-30% GREASE232.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - S235.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H238.3 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - S244.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - S274.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - S274.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped278.2 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H316.5 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - S343.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H349.3 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish - SLIGHT349.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB349.3 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT349.8 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (6)

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - H

    15.5 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - H

  • General Observation - 15" VCP

    141.7 ft. - General Observation - 15" VCP

  • Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    151.5 ft. - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    151.5 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Photograph

    226.7 ft. - General Photograph

  • Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    226.7 ft. - Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (49)

DistanceCodeObservation
122.1TFCCapped
85.8FCH
227TFDOPEN-30% GREASE
226.7MGP
12.9FCHAIRLINE
151.5FCS
0MGOConn. @ Mh, 9 O' Clock. Active
232.5FCS
235.2FCH
0MGOConn. @ Mh, 3 O' Clock. OPEN
130.1FCH
316.5FCS
278.2FCH
15.5FSH
157.6FSH
238.3FCS
244.3FCS
0MWL
151.5FSH
349.3FSSLIGHT
82.1FCH
87.8FCH
0AMH3:55AM
151.5FSSLIGHT
141.7MGO15" VCP
205.1FCS
85.8FCH
179TFCCapped
151.5FCH
160.4FCS
274.7FLS
0MWM
172.7FCS
349.8AMH4:55AM
343.3FCH
74.1TFActive
221FCS
349.3MGOConn. @ Mh, 3 O' Clock. STUB
13.5FCH
157.6FCH
38.2FCH
349.3FSSLIGHT
15.5FSH
38.2TFCCapped
274.7TFCCapped
115.9FLH
226.7DAGS
82.1FCH
151.5FSSLIGHT

Properties (6)

custom_field_three
SLIGHT SPRIAL FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-09-30T03:40:31-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false