Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2016, 05:28 PM
  • 29 0115_29 0086_9192016_105650.mp4

Date
09/19/2016
W/O
0586011
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00273
PipeID
P23902
Time
10:28 AM
Certificate
U-115-06022628
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7235
Sewer Name
29 33RD STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20160919MI_33_RD_STREET_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0115
Downstream MH
29 0086
Dir. of Survey
Downstream
Length Surveyed
292 ft.
Total Length
292 ft.
Structural Index
3
Structural Quick
513B
Structural Rating
50
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
57
Pipe schematic from manhole 29 0115 to 29 0086
MH: 29 0115MH: 29 0086downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Downstream Manhole, Survey Begins - 10:55AM0 ft. MWL - Water Level, 10 %of cross sectional area8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"10.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"25 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES25 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES51.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES62.4 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES64.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"64.8 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES67.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"68.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES93.1 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES115.3 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"116.2 ft. RMJ - Roots Medium Joint, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YESR118.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 90 %134.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES139.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES140.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES149.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES165.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"168.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"177.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"200.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES215.9 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES216.2 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"219.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"241.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES260.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES267.2 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 25%269.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"277.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES291.7 ft. BVV - Broken Void Visible, from 11 to 02 o'clock, within 8 inches of joint: YES292 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES292 ft. AOC - Drop Connection, Survey Ends - ZOOMED DUE TO BROKEN PIPE AT 12 OCLOCK

Observation photos (10)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    25 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    51.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    62.4 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YESR

    116.2 ft. - Roots Medium Joint, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YESR

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 90 %

    118.1 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 90 %

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    139.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 25%

    267.2 ft. - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS, 25%

  • Broken Void Visible, from 11 to 02 o'clock, within 8 inches of joint: YES

    291.7 ft. - Broken Void Visible, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    292 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Drop Connection, Survey Ends - ZOOMED DUE TO BROKEN PIPE  AT 12 OCLOCK

    292 ft. - Drop Connection, Survey Ends - ZOOMED DUE TO BROKEN PIPE AT 12 OCLOCK

Observations (36)

DistanceCodeObservation
8TFC
267.2TFAROOTS, 25%
0MWM
0AMH10:55AM
134.2CM
68.7CM
118.1TFDROOTS, 90 %
292CM
292AOCZOOMED DUE TO BROKEN PIPE AT 12 OCLOCK
139.1CL
25DAGS
219.2TFC
241.6CM
93.1CM
140.9CM
269.7TFC
165.8TFA
200.3CM
260.6CM
116.2RMJ
177.2TFA
62.4CM
215.9CL
168.3TFC
64.8TFA
64.8CM
67.2TFA
291.7BVV
10.1TFA
51.8CM
0MWL
216.2TFA
149.4CM
25CL
277.4CM
115.3TFA

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2016-09-19T10:28:41-07:00
documentation
IGNACIO, FRANKLIN, SHADLER, BRAR
is_lateral_inspection
false