Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2016, 12:01 PM
  • 05 0861_08 0860_9222016_051035.mp4

Date
09/22/2016
W/O
0585472
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00457
PipeID
P06091
Time
5:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0290
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
20160919MDM_IMPERIAL_HIGHWAY_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0861
Downstream MH
08 0860
Dir. of Survey
Downstream
Length Surveyed
132.8 ft.
Total Length
132.8 ft.
Structural Index
2
Structural Quick
3326
Structural Rating
22
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 0861 to 08 0860
MH: 05 0861MH: 08 0860downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start42.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE63 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT65.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H69.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H75.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H79.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped80.7 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - S81.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped83.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - S101.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H107.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - S116.1 ft. JOM - Joint Offset Medium132.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN132.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish132.8 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Joint Offset Medium

    116.1 ft. - Joint Offset Medium

Observations (21)

DistanceCodeObservation
0AMH5:10AM
42.1FLHAIRLINE
81.5TFCCapped
116.1JOM
75.3FLH
63FCSLIGHT
69.1FCH
83.2FLS
0MGOConn. @ Mh, 9 O' Clock. Capped
132.8AMH5:30AM
132.1MGOConn. @ Mh, 9 O' Clock. OPEN
0MWM
2DAGS
80.7FCS
0MWL
101.9FCH
65.9FCH
79.1TFCCapped
132.1DAGS
0MGOConn. @ Mh, 3 O' Clock. Capped
107.7FCS

Properties (6)

custom_field_three
SLIGHT FRACTURE
custom_field_two
4
customer
LACSD
datetime
2016-09-22T05:01:56-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection