Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2016, 07:55 AM
  • 05 0877_05 0876_9202016_010754.mp4

Date
09/20/2016
W/O
0585472
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00457
PipeID
P06108
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0285
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
LENNOX
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
20160919MDM_IMPERIAL_HIGHWAY_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0876
Downstream MH
05 0877
Dir. of Survey
Upstream
Length Surveyed
263.5 ft.
Total Length
263.5 ft.
Structural Index
2
Structural Quick
362B
Structural Rating
52
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
54
Pipe schematic from manhole 05 0876 to 05 0877
MH: 05 0876MH: 05 0877upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:35AM0.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped3.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - S3.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H16 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H25.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H38.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open70.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT71.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open 80% GREASE74 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped78.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H84.9 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - H84.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H118.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H145.6 ft. MGO - General Observation - 10: VCP164.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES185.5 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H194.8 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - H206.8 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - H206.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H216 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H216 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H225 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H225 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H225 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H232.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open234.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped236 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H236 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H245.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE245.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE263.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active263.5 ft. MWM - Water Mark, 30 %of cross sectional area263.5 ft. MGO - General Observation - Conn. @ Mh, 4 O' Clock. Active263.5 ft. AMH - Downstream Manhole, Survey Begins - 12:55AM263.5 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • General Observation - 10: VCP

    117.9 ft. - General Observation - 10: VCP

Observations (36)

DistanceCodeObservation
184.6FCH
178.6FCH
78FCH
29.2TFCCapped
192.7FCSLIGHT
27.5FCH
224.8TBOpen
259.7FCS
38.5FCH
189.5TFCCapped
259.7FCH
191.7TFDOpen 80% GREASE
0MGOConn. @ Mh, 3 O' Clock. Active
47.5FCH
0MWM
18.2FCHAIRLINE
178.6FLH
18.2FCHAIRLINE
0MGOConn. @ Mh, 4 O' Clock. Active
263.1MGOConn. @ Mh, 3 O' Clock. Capped
117.9MGO10: VCP
263.5AMH1:35AM
31.3TFOpen
38.5FLH
68.7FCH
56.7FCH
144.9FCH
99.1CL
27.5FLH
0AMH12:55AM
238.3FLH
0MWL
47.5FCH
247.5FCH
38.5FLH
56.7FLH

Properties (6)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-09-20T00:55:00-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false