Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2016, 07:41 AM
  • 05 0881_05 0880_9192016_023206.mp4

Date
09/19/2016
W/O
0585472
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00457
PipeID
P06112
Time
12:41 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0284
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
LENNOX
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
20160919MDM_IMPERIAL_HIGHWAY_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0880
Downstream MH
05 0881
Dir. of Survey
Upstream
Length Surveyed
53.9 ft.
Total Length
53.9 ft.
Structural Index
2
Structural Quick
3329
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
29
Pipe schematic from manhole 05 0880 to 05 0881
MH: 05 0880MH: 05 0881upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:45AM0.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN2.3 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H15.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H15.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H21.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H21.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H24.4 ft. CC - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES26 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open27.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H33.7 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - H36.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H39.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H42.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT45.9 ft. MGO - General Observation - 10" VCP47.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE47.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE53.9 ft. MGO - General Observation - Conn. @ Mh, 8 O' Clock. STUB53.9 ft. MWM - Water Mark, 20 %of cross sectional area53.9 ft. AMH - Downstream Manhole, Survey Begins - 3:30AM53.9 ft. MWL - Water Level, 10 %of cross sectional area53.9 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN

Observation photos (1)

  • General Observation - 10" VCP

    8 ft. - General Observation - 10" VCP

Observations (23)

DistanceCodeObservation
44.9FCH
0MGOConn. @ Mh, 8 O' Clock. STUB
11.2FCSLIGHT
53.5MGOConn. @ Mh, 9 O' Clock. OPEN
0MWM
17.1FLH
32.6FCH
38.6FCH
27.9TBOpen
53.9AMH3:45AM
20.2FCH
14.6FCH
0AMH3:30AM
6FLHAIRLINE
0MWL
8MGO10" VCP
0MGOConn. @ Mh, 9 O' Clock. OPEN
29.5CC
6FLHAIRLINE
51.6CC
32.6FCH
26.5FCH
38.6FCH

Properties (6)

custom_field_three
HAIRLINES
custom_field_two
4
customer
LACSD
datetime
2016-09-19T00:41:20-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false