Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2016, 10:32 AM
  • 05 0846_05 0845_9172016_052603.mp4

Date
09/17/2016
W/O
0585473
Weather
Dry
Operator/Surveyor
OLIVER
Sewer ID
Z00457
PipeID
P06076
Time
3:32 AM
Certificate
U-415-06024036
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0282
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
LENNOX
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
20160917RO_IMPERIAL_HIGHWAY_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 0846
Downstream MH
05 0845
Dir. of Survey
Downstream
Length Surveyed
323.3 ft.
Total Length
323.3 ft.
Structural Index
2
Structural Quick
3615
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
23
Pipe schematic from manhole 05 0846 to 05 0845
MH: 05 0846MH: 05 0845downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:25 AM62.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"77.9 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES85.5 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES89.2 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES91 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES100.5 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES102.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"111.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4"116.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES118.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"142.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"164.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES169.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES182.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4"202 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES212.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES231.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"240 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"243.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"249.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES258.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"323.3 ft. AMH - Downstream Manhole, Survey Ends - 6:11 AM323.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 10"323.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 10"

Observations (28)

DistanceCodeObservation
182.7TF
142.3TF
240TF
0MWM
249.8CM
62.1TF
243.8TB
169.2CM
0MWL
231.6TF
212.3CM
89.2CC
102.1TF
85.5CC
116.1CM
323.3AMH6:11 AM
118.3TF
258.8TF
77.9CC
111.2TB
69.3TF
0AMH5:25 AM
100.5CC
323.3TF
164.2CM
202CM
323.3TF
91CC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2016-09-17T03:32:22-07:00
documentation
OLIVER, MANAMES, REVELES
is_lateral_inspection
false