Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 08:46 AM
  • 32 1007_32 1255 _02112020_005729.mp4

Date
02/11/2020
W/O
808212
Weather
Dry
Operator/Surveyor
S . LOPEZ
Sewer ID
Z00841
PipeID
P19455
Time
12:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7505
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_808212_TV32064_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1007
Downstream MH
32 1255
Dir. of Survey
Downstream
Length Surveyed
113.7 ft.
Total Length
113.7 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
51
O&M Index
2
O&M Quick
2C00
O&M Rating
44
Overall Index
2
Overall Quick
Overall Rating
95
Pipe schematic from manhole 32 1007 to 32 1255
MH: 32 1007MH: 32 1255downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK - 20% OF CONN. OBSTRUCTED BY DEBRIS0 ft. AMH - Upstream Manhole, Survey Begins - 32 10070 ft. MWM - Water Mark, 40 %of cross sectional area1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"27.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start112.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish112.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish113.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1255

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    27.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
112.3DAGS
0MWL
112.3CM
1.9DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK - 20% OF CONN. OBSTRUCTED BY DEBRIS
27.6CM
113.7AMH32 1255
12.9TBA
0AMH32 1007
0MWM

Properties (6)

additional_info
SC 389794
custom_field_two
3
customer
LACSD
datetime
2020-02-11T00:46:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false