- Date
- 02/04/2020
- W/O
- 808190
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00520
- PipeID
- P05885
- Time
- 10:00 PM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7301
- Sewer Name
- 05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
- City
- INGLEWOOD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_808190_TV05343_JAN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 05 0659
- Downstream MH
- 05 0660
- Dir. of Survey
- Upstream
- Length Surveyed
- 294.1 ft.
- Total Length
- 294.1 ft.
- Structural Index
- 3
- Structural Quick
- 5131
- Structural Rating
- 12
- O&M Index
- 3
- O&M Quick
- 3300
- O&M Rating
- 9
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 21
Pipe schematic from manhole 05 0659 to 05 0660 Observation photos (4)

4 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

29.4 ft. - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: NO - WALL DAMAGE & 2 UNKNOWN OBJECTS VISIBLE

141.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

273.6 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES