Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2020, 06:58 AM
  • H 1289_H 1288 _01292020_231614.mp4

Date
01/29/2020
W/O
808197
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01183
PipeID
P17305
Time
10:58 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7291
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_808197_TV22154_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1288
Downstream MH
H 1289
Dir. of Survey
Upstream
Length Surveyed
311.8 ft.
Total Length
311.8 ft.
Structural Index
3
Structural Quick
543K
Structural Rating
325
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
447
Pipe schematic from manhole H 1288 to H 1289
MH: H 1288MH: H 1289upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - H 12892.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish10 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start73.3 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish83.1 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start309.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start309.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start309.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start311.8 ft. MWM - Water Mark, 30 %of cross sectional area311.8 ft. MWL - Water Level, 20 %of cross sectional area311.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE311.8 ft. AMH - Downstream Manhole, Survey Begins - H 1288

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

    228.7 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    301.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    311.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
309.4DAGS
311.8MGOCOCKROACHES IN MANHOLE
0MWM
309.4SSS
301.8SRV
0MWL
238.5SRV
2SAP
311.8MGOCONNECTION AT MH 9 O'CLOCK
2SSS
0MGOCOCKROACHES IN MANHOLE
2DAGS
309.4SAP
309.4SRV
311.8AMHH 1289
0AMHH 1288
228.7SRV

Properties (6)

additional_info
SC398777
custom_field_two
2
customer
LACSD
datetime
2020-01-29T22:58:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false