Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2020, 06:01 AM
  • H 1286_H 1285 _01292020_221138.mp4

Date
01/29/2020
W/O
808197
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01183
PipeID
P17302
Time
10:01 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7291
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_808197_TV22154_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1286
Downstream MH
H 1285
Dir. of Survey
Downstream
Length Surveyed
328.3 ft.
Total Length
328.3 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
322
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
452
Pipe schematic from manhole H 1286 to H 1285
MH: H 1286MH: H 1285downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 12860 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start76.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"288.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"325 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish326.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish326.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE328.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK328.3 ft. AMH - Downstream Manhole, Survey Ends - H 1285

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    328.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
7SAV
328.3MGOCOCKROACHES IN MANHOLE
0AMHH 1286
326.2DAGS
0MWM
0MWL
76.8TFC
2SSS
165.2TFC
220.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK
328.3MGOCONNECTION AT MH 3 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
328.3AMHH 1285
84.4TFC
325SAV
326.2SSS
2DAGS
288.8TB

Properties (6)

additional_info
SC398777
custom_field_two
3
customer
LACSD
datetime
2020-01-29T22:01:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false