Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 08:58 AM
  • 05 1600_05 1599 _02052020_011742.mp4

Date
02/05/2020
W/O
808191
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00485
PipeID
P06824
Time
12:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7303
Sewer Name
05 MARICOPA STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_808191_TV05344_JAN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1599
Downstream MH
05 1600
Dir. of Survey
Upstream
Length Surveyed
313.4 ft.
Total Length
313.4 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
310
Pipe schematic from manhole 05 1599 to 05 1600
MH: 05 1599MH: 05 1600upstream0 ft. MGO - General Observation - OPEN CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 16002.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. MWL - Water Level, 25 %of cross sectional area18.4 ft. MGO - General Observation - 5% DEBRIS IN LINE FROM 4 TO 8 O'CLOCK119.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"168.4 ft. TFA - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"275.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start311.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start313.4 ft. MWL - Water Level, 5 %of cross sectional area313.4 ft. MWM - Water Mark, 25 %of cross sectional area313.4 ft. AMH - Downstream Manhole, Survey Begins - 05 1599

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
84.9TFC
80.9TFC
310.5MWL
145TFA
0MWL
313.4MGOOPEN CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0MWM
2SAP
33.5TFC
310.9DAGS
193.7TBA
310.9SAP
313.4AMH05 1600
0AMH05 1599
37.7TFA
141.3TFA
295MGO5% DEBRIS IN LINE FROM 4 TO 8 O'CLOCK
2DAGS

Properties (6)

additional_info
SC398788
custom_field_two
3
customer
LACSD
datetime
2020-02-05T00:58:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false