Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2019, 11:28 AM
  • Section#4_22 0750_22 0749__1272019__I0286.mp4

Date
12/07/2019
W/O
0798221
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00821
PipeID
P17107
Time
3:28 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
I0286
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20191207MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0750
Downstream MH
22 0749
Dir. of Survey
Downstream
Length Surveyed
356.7 ft.
Total Length
356.7 ft.
Structural Index
4
Structural Quick
4N00
Structural Rating
292
O&M Index
2
O&M Quick
3212
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
300
Pipe schematic from manhole 22 0750 to 22 0749
MH: 22 0750MH: 22 0749downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 80% START23.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB101.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB151.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB200.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB206.6 ft. RMJ - Roots Medium Joint, from 12 to 05 o'clock, 25 %, within 8 inches of joint: YESR253.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB266.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG272 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR276.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%279.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%308.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB348.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE350.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG350.3 ft. MGO - General Observation - MAG COAT 80% FINISH356.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG356.7 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (6)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 80% START

    2 ft. - General Observation - MAG COAT 80% START

  • Roots Medium Joint, from 12 to 05 o'clock, 25 %, within 8 inches of joint: YESR

    206.6 ft. - Roots Medium Joint, from 12 to 05 o'clock, 25 %, within 8 inches of joint: YESR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    266.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    272 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    350.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (21)

DistanceCodeObservation
2SAMSEVERE AGG
0AMH3:35AM
200.4TFCSTUB
356.7AMH4:35AM
101.6TFCSTUB
23.5TFCSTUB
279.4RFJ3%
350.3SAMSEVERE AGG
206.6RMJ
2MGOMAG COAT 80% START
151.5TFCSTUB
272RMJ
266.9SAMSEVERE AGG
308.3TFCSTUB
0MWM
253.3TFCSTUB
350.3MGOMAG COAT 80% FINISH
348.7TFAACTIVE
356.3SAMSEVERE AGG
0MWL
276.2RFJ3%

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2019-12-07T03:28:02-08:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false