Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 12, 2020, 08:32 AM
  • J 0044_J 0042_2122020_012002.mp4

Date
02/12/2020
W/O
0808067
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00062
PipeID
P11621
Time
12:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1354
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20100211MDM_JOINT_OUTFALL_J_UNIT_2C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
J 0044
Downstream MH
J 0042
Dir. of Survey
Downstream
Length Surveyed
369.7 ft.
Total Length
369.7 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole J 0044 to J 0042
MH: J 0044MH: J 0042downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM2 ft. MGO - General Observation - MAG COAT 95% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE24.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE175.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE369.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active369.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLIISTERING PEELING CONCRETE369.2 ft. MGO - General Observation - MAG COAT 95% FINISH369.7 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (4)

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    24.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    175.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (12)

DistanceCodeObservation
369.2MGOConn. @ Mh, 9 O' Clock. Active
24.9SSSBLISTERING CONCRETE
2MGOMAG COAT 95% START
0MWM
369.2SSSBLIISTERING PEELING CONCRETE
369.2MGOMAG COAT 95% FINISH
2SSSBLISTERING PEELING CONCRETE
0MGOConn. @ Mh, 9 O' Clock. Active
175.1SSSBLISTERING PEELING CONCRETE
0MWL
0AMH12:55AM
369.7AMH1:25AM

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE-95% MAG
custom_field_two
3
customer
LACSD
datetime
2020-02-12T00:32:54-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false