Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 11:43 AM
  • J 0056_J 0053_2112020_040109.mp4

Date
02/11/2020
W/O
0808067
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00062
PipeID
P11633
Time
3:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1353
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20100211MDM_JOINT_OUTFALL_J_UNIT_2C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
J 0056
Downstream MH
J 0053
Dir. of Survey
Downstream
Length Surveyed
691.9 ft.
Total Length
691.9 ft.
Structural Index
4
Structural Quick
5343
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole J 0056 to J 0053
MH: J 0056MH: J 0053downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 95% START16.1 ft. MGO - General Observation - 80% MAG COAT START16.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG72.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG92.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR POSSIBLE122.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 8" - Active264.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG599.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR627.2 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR691.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE691.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG MISSING691.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active691.4 ft. MGO - General Observation - 70% MAG COAT FINISH691.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (7)

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    16.1 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    72.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR POSSIBLE

    92.9 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR POSSIBLE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    264.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    599.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    627.2 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (18)

DistanceCodeObservation
72.3SAMSEVERE AGG
16.1MGO80% MAG COAT START
691.9AMH5:00AM
92.9SRVLONG REBAR POSSIBLE
599.9SRVCIRCUM REBAR
264.8SAMSEVERE AGG
691.4SSSBLISTERING PEELING CONCRETE
627.2SRVCIRCUM REBAR
16.1SAMSEVERE AGG
122.2TFAActive
0MWL
691.4SAMSEVERE AGG MISSING
0AMH4:10AM
2SSSBLISTERING PEELING CONCRETE
691.4MGOConn. @ Mh, 3 O' Clock. Active
691.4MGO70% MAG COAT FINISH
2MGOMAG COAT 95% START
0MWM

Properties (6)

custom_field_three
LONG & CIRCUM REBAR VISIBLE SPORATIC-70% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2020-02-11T03:43:51-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false