Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 11:43 AM
  • 15 0359_15 0358_252020_034541.mp4

Date
02/05/2020
W/O
0812851
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00598
PipeID
P12285
Time
3:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1348
Sewer Name
15 BALDWIN PARK TRUNK
City
BALWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20200105MDM_BALWIN_PARK_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
15 0359
Downstream MH
15 0358
Dir. of Survey
Downstream
Length Surveyed
399.8 ft.
Total Length
399.8 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
13
O&M Index
3
O&M Quick
4221
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 15 0359 to 15 0358
MH: 15 0359MH: 15 0358downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG4.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open4.9 ft. MGO - General Observation - MAG COAT 20% START11.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED17.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG20 ft. SSS - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED37.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped41.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open114.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped118.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open167.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped172.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped225.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED233.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped254.5 ft. MWM - Water Mark, 60 %of cross sectional area265.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCK270.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped296.9 ft. MWM - Water Mark, 40 %of cross sectional area318.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped322.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped371.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped376 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped399.3 ft. MGO - General Observation - 20% MAG COAT FINISH399.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG399.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG399.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE399.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED399.8 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 20% START

    4.9 ft. - General Observation - MAG COAT 20% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    11.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    17.3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    20 ft. - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (33)

DistanceCodeObservation
41.5TFOpen
172.5TFCCapped
265.7DSZROCK
399.3MGO20% MAG COAT FINISH
17.3SAMSEVERE AGG
399.3SAVSEVERE AGG
20SSSPEELING CONCRETE SEVERE AGG ATTACHED
399.8AMH4:15AM
376TFCCapped
322.5TFCCapped
4.9TFOpen
254.5MWM
0MWL
2SSSBLISTERING FLAKING CONCRETE
225.1TFCCAPPED
2SAVSEVERE AGG
233.1TFCCapped
399.3SAMSEVERE AGG
371.6TFCCapped
37.9TFCCapped
167.9TFCCapped
4.9MGOMAG COAT 20% START
296.9MWM
318.9TFCCapped
0AMH3:45AM
399.3SSSBLISTERING FLAKING CONCRETE
270.1TFCCapped
0MWM
11.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
399.3SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MGOConn. @ Mh, 9 O' Clock. Active
114.7TFCCapped
118.8TFOpen

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2020-02-05T03:43:01-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false