Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 11:14 AM
  • 15 0360_15 0359_252020_032228.mp4

Date
02/05/2020
W/O
0812851
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00598
PipeID
P12286
Time
3:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1348
Sewer Name
15 BALDWIN PARK TRUNK
City
BALWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20200105MDM_BALWIN_PARK_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
15 0360
Downstream MH
15 0359
Dir. of Survey
Downstream
Length Surveyed
175.6 ft.
Total Length
175.6 ft.
Structural Index
2
Structural Quick
3224
Structural Rating
14
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 15 0360 to 15 0359
MH: 15 0360MH: 15 0359downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE9.3 ft. SSS - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE41.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped45.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped67.9 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE68.9 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED94.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped114.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped134.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER4E AGG139 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6" - Capped143.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped150.8 ft. MGO - General Observation - 10% MAG COAT START175 ft. MGO - General Observation - 10% MAG COAT FINIAH175 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG175 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING PEELING CONCRETE175 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active175.6 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (6)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

    9.3 ft. - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    67.9 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    68.9 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER4E AGG

    134.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER4E AGG

Observations (21)

DistanceCodeObservation
139TFCCapped
175MGO10% MAG COAT FINIAH
68.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWM
0MWL
143.1TFCCapped
2SAVSEVERE AGG
9.3SSSFLAKING CONCRETE
0AMH3:20AM
41.2TFCCapped
134.3SAVSEVER4E AGG
175SAVSEVERE AGG
94.1TFCCapped
2SSSBLISTERING FLAKING CONCRETE
175SSSBLISTERING FLAKING PEELING CONCRETE
175.6AMH3:40AM
175MGOConn. @ Mh, 9 O' Clock. Active
67.9SSSPEELING CONCRETE
114.6TFCCapped
150.8MGO10% MAG COAT START
45.4TFCCapped

Properties (6)

custom_field_three
SEVERE AGG VISIBLE
custom_field_two
3
customer
LACSD
datetime
2020-02-05T03:14:56-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false