- Date
- 02/05/2020
- W/O
- 0812851
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00598
- PipeID
- P12287
- Time
- 2:28 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1348
- Sewer Name
- 15 BALDWIN PARK TRUNK
- City
- BALWIN PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 18
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200105MDM_BALWIN_PARK_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 15 0361
- Downstream MH
- 15 0360
- Dir. of Survey
- Downstream
- Length Surveyed
- 80.8 ft.
- Total Length
- 80.8 ft.
- Structural Index
- 2
- Structural Quick
- 3122
- Structural Rating
- 7
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 15 0361 to 15 0360 Observation photos (4)

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - General Observation - MAG COAT 30% START

21.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRTE