Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 09:36 AM
  • 15 0363_18 0262_252020_014513.mp4

Date
02/05/2020
W/O
0812851
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00598
PipeID
P12289
Time
1:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1348
Sewer Name
15 BALDWIN PARK TRUNK
City
BALWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20200105MDM_BALWIN_PARK_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
15 0363
Downstream MH
15 0362
Dir. of Survey
Downstream
Length Surveyed
237.8 ft.
Total Length
237.8 ft.
Structural Index
3
Structural Quick
3522
Structural Rating
19
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 15 0363 to 15 0362
MH: 15 0363MH: 15 0362downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. MGO - General Observation - MAG COAT 50% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE16.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER AGG26.5 ft. MWM - Water Mark, 50 %of cross sectional area49.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped53.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG61.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open87.6 ft. MGO - General Observation - 70% MAG COAT START94.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open101.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Active119.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE138.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped143.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped174.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG204.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped229.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG237.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active237.3 ft. MGO - General Observation - 70% MAG COAT FINISH237.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG237.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG237.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE237.8 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (9)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 50% START

    2 ft. - General Observation - MAG COAT 50% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER AGG

    16.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVER AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    53.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 70% MAG COAT START

    87.6 ft. - General Observation - 70% MAG COAT START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    119.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    174.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    229.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (27)

DistanceCodeObservation
237.3MGOConn. @ Mh, 9 O' Clock. Active
0AMH1:40AM
26.5MWM
16.9SAVSEVER AGG
237.3MGO70% MAG COAT FINISH
0MGOConn. @ Mh, 3 O' Clock. Active
61.6TFOpen
0MWM
53.5SAVSEVERE AGG
143.1TFCCapped
0MWL
237.8AMH2:05AM
2SAVSEVERE AGG SPORATIC
174.9SAVSEVERE AGG
229.8SAVSEVERE AGG
94.2TFOpen
87.6MGO70% MAG COAT START
138.9TFCCapped
2MGOMAG COAT 50% START
237.3SAVSEVERE AGG
101.9TFAActive
237.3SAVSEVERE AGG
204.7TFCCapped
49.2TFCCapped
119.7SSSBLISTERING CONCRETE
237.3SSSBLISTERING FLAKING CONCRETE
2SSSBLISTERING FLAKING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG VISIBLE
custom_field_two
3
customer
LACSD
datetime
2020-02-05T01:36:38-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false