Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 08:23 AM
  • 15 0365_15 0364_252020_010831.mp4

Date
02/05/2020
W/O
0812851
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00598
PipeID
P12291
Time
12:23 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1348
Sewer Name
15 BALDWIN PARK TRUNK
City
BALWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20200105MDM_BALWIN_PARK_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
15 0365
Downstream MH
15 0364
Dir. of Survey
Downstream
Length Surveyed
192.9 ft.
Total Length
192.9 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 15 0365 to 15 0364
MH: 15 0365MH: 15 0364downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - MAG COAT 70% START0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE CONCRETE2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG31.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE44.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active51.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG80.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped97.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open100.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG117.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open150.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open154.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped177.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Active192.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG192.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE192.6 ft. MGO - General Observation - MAG COAT 70% FINISH192.9 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (6)

  • General Observation - MAG COAT 70% START

    0 ft. - General Observation - MAG COAT 70% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

    31.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    51.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    100.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (21)

DistanceCodeObservation
0MWM
100.3SAVSEVERE AGG
154.6TFCCapped
0MGOMAG COAT 70% START
192.6SAVSEVERE AGG
192.6SSSBLISTERING FLAKING CONCRETE
192.9AMH1:10AM
0MGOConn. @ Mh, 9 O' Clock. Active
177.7TFActive
51.3SAVSEVERE AGG
0AMH12:45AM
44.1TFActive
2SSSBLISTERING FLAKING CONCRETE CONCRETE
2SAVSEVERE AGG
0MWL
150.2TFOpen
192.6MGOMAG COAT 70% FINISH
97.2TFOpen
117.6TFOpen
31.5SSSFLAKING CONCRETE
80.9TFCCapped

Properties (6)

custom_field_three
SEVERE AGG VISIBLE
custom_field_two
3
customer
LACSD
datetime
2020-02-05T00:23:13-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false