Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2019, 10:43 AM
  • 02 0158_02 0157 _12032019_030535.mp4

Date
12/03/2019
W/O
798204
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02461
Time
2:43 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7138
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_798204_TV02383_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 0158
Downstream MH
02 0157
Dir. of Survey
Downstream
Length Surveyed
376.7 ft.
Total Length
376.7 ft.
Structural Index
3
Structural Quick
3L22
Structural Rating
205
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
357
Pipe schematic from manhole 02 0158 to 02 0157
MH: 02 0158MH: 02 0157downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01582 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start128 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"241.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.9 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"294.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"374.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish374.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish375 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0157376.7 ft. MGO - General Observation - COCKROACHES AT MH376.7 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    41.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

    242.9 ft. - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

  • General Observation - COCKROACHES AT MH

    376.7 ft. - General Observation - COCKROACHES AT MH

Observations (20)

DistanceCodeObservation
197.9TBA
374.6DAGS
376.7AMH02 0157
0MWM
128TFC
0MWL
192.9TFC
294.6TFC
376.7MGOCOCKROACHES AT MH
375SSS
2DAGS
2SSS
376.7MGOCONN @ MH 3 O'CLOCK/ACTIVE
297.1TFC
241.9TFC
0AMH02 0158
41.9CM
242.9TFI
195.9TFC
374.6CM

Properties (6)

additional_info
SC378870
custom_field_two
3
customer
LACSD
datetime
2019-12-03T02:43:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false