Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2020, 06:06 AM
  • 02 0430_02 0429 _02032020_223212.mp4

Date
02/03/2020
W/O
808198
Weather
Very Dry
Operator/Surveyor
S LOPEZ
Sewer ID
Z00312
PipeID
P02753
Time
10:06 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7299
Sewer Name
02 70TH WAY EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_808198_TV02338_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0430
Downstream MH
02 0429
Dir. of Survey
Downstream
Length Surveyed
324.5 ft.
Total Length
324.5 ft.
Structural Index
2
Structural Quick
312M
Structural Rating
143
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
275
Pipe schematic from manhole 02 0430 to 02 0429
MH: 02 0430MH: 02 0429downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 04300 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"7.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"55.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"64.2 ft. CS - Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES87.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start103.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"110.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish151.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"205.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"253 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"256 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES305.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"322 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish322.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4" - @ MH324.5 ft. ACOM - Cleanout Mainline, Survey Ends - 02 0429

Observations (23)

DistanceCodeObservation
0MWL
305.3TFA
7.2TFC
253TFC
205.4TFC
0AMH02 0430
322.2DAGS
0MWM
324TFA@ MH
2DAGS
2DAGS
323SSS
110.5CL
151.2TFA
103.6TFC
324.5ACOM02 0429
87.5CL
2SSS
256CM
55.3TFC
3.8TBA
322DAGS
64.2CS

Properties (6)

additional_info
SC398784
custom_field_two
3
customer
LACSD
datetime
2020-02-03T22:06:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false