Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 17, 2020, 07:07 AM
  • 18 0488_18 1194 _01162020_231436.mp4

Date
01/16/2020
W/O
808210
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00687
PipeID
P15040
Time
11:07 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7276
Sewer Name
18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_808210_TV18109_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1194
Downstream MH
18 0488
Dir. of Survey
Upstream
Length Surveyed
95.2 ft.
Total Length
95.2 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
54
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 18 1194 to 18 0488
MH: 18 1194MH: 18 0488upstream0 ft. MGO - General Observation - STOP LOG0 ft. AMH - Upstream Manhole, Survey Ends - 18 04880.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish91.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start93.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start95.2 ft. MWM - Water Mark, 15 %of cross sectional area95.2 ft. AMH - Downstream Manhole, Survey Begins - 18 119495.2 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - STOP LOG

    95.2 ft. - General Observation - STOP LOG

Observations (9)

DistanceCodeObservation
94.2CM
95.2MGOSTOP LOG
2DAGS
95.2AMH18 0488
0MWM
94.3DAGS
0AMH18 1194
3.3CM
0MWL

Properties (7)

additional_info
SC398761
custom_field_two
2
customer
LACSD
datetime
2020-01-16T23:07:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31671