Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 17, 2020, 06:59 AM
  • 18 1194_18 1193 _01162020_230745.mp4

Date
01/16/2020
W/O
808210
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00687
PipeID
P15039
Time
10:59 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7276
Sewer Name
18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_808210_TV18109_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1193
Downstream MH
18 1194
Dir. of Survey
Upstream
Length Surveyed
243.5 ft.
Total Length
243.5 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
234
Pipe schematic from manhole 18 1193 to 18 1194
MH: 18 1193MH: 18 1194upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 11941.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish232.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start243.5 ft. AMH - Downstream Manhole, Survey Begins - 18 1193243.5 ft. MWL - Water Level, 5 %of cross sectional area243.5 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
10.7CM
242.3CM
0AMH18 1193
0MWL
243.5AMH18 1194
242.3DAGS
2DAGS
0MWM

Properties (7)

additional_info
SC398761
custom_field_two
2
customer
LACSD
datetime
2020-01-16T22:59:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31671