Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 17, 2020, 06:04 AM
  • 18 1191_18 1190 _01162020_222101.mp4

Date
01/16/2020
W/O
808210
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00687
PipeID
P15036
Time
10:04 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7276
Sewer Name
18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_808210_TV18109_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1191
Downstream MH
18 1190
Dir. of Survey
Downstream
Length Surveyed
423.3 ft.
Total Length
423.3 ft.
Structural Index
3
Structural Quick
4B3L
Structural Rating
261
O&M Index
2
O&M Quick
2P00
O&M Rating
168
Overall Index
3
Overall Quick
Overall Rating
429
Pipe schematic from manhole 18 1191 to 18 1190
MH: 18 1191MH: 18 1190downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11910 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start25.3 ft. CS - Crack Spiral, from 06 to 12 o'clock, within 8 inches of joint: NO28.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start316 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES322.3 ft. FM - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES346.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start346.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish421.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish423.3 ft. AMH - Downstream Manhole, Survey Ends - 18 1190423.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    316 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    322.3 ft. - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    346.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
316FS
0AMH18 1191
28.3CM
25.3CS
421.8FM
322.3FM
423.3AMH18 1190
0MWM
346.9FM
0MWL
346.9CM
423.3DAGS
2DAGS

Properties (7)

additional_info
SC398761
custom_field_two
2
customer
LACSD
datetime
2020-01-16T22:04:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31671