Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2020, 09:43 AM
  • 14 0231A_14 0231_01232020_020313.mp4

Date
01/23/2020
W/O
808200
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00575
PipeID
P18282
Time
1:43 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7283
Sewer Name
14 NORTH SIDE TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_808200_TV14057_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0231A
Downstream MH
14 0231
Dir. of Survey
Downstream
Length Surveyed
422.3 ft.
Total Length
422.3 ft.
Structural Index
2
Structural Quick
3422
Structural Rating
17
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 14 0231A to 14 0231
MH: 14 0231AMH: 14 0231downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 0231A0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area15 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES16.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"27.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES51 ft. JSL - Joint Separated Large - SOIL VISIBLE51 ft. JOM - Joint Offset Medium57.3 ft. JAL - Joint Angular Large75.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.2 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES137.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"200.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"256.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES258 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"320.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURED CAP414.3 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 05 to 07 o'clock - ROD422.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0231

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    15 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    27.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Joint Separated Large - SOIL VISIBLE

    51 ft. - Joint Separated Large - SOIL VISIBLE

  • Joint Offset Medium

    51 ft. - Joint Offset Medium

  • Joint Angular Large

    57.3 ft. - Joint Angular Large

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    136.2 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    256.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Obstacles Other, 20 %of cross sectional area, from 05 to 07 o'clock - ROD

    414.3 ft. - Obstacles Other, 20 %of cross sectional area, from 05 to 07 o'clock - ROD

Observations (19)

DistanceCodeObservation
258TFC
15CM
422.3AMH14 0231
27.8CM
75.6TFC
0AMH14 0231A
16.5TFC
0MWL
136.2CM
200.4TFC
0MWM
51JSLSOIL VISIBLE
414.3OBZROD
51JOM
137.3TFC
57.3JAL
378.4TFCFRACTURED CAP
320.2TFC
256.3CM

Properties (6)

additional_info
SC398768
custom_field_two
1
customer
LACSD
datetime
2020-01-23T01:43:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false