Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2016, 11:12 AM
  • 05 0817_05 0816 _11292016_031311.mp4

Date
11/29/2016
W/O
602600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00419
PipeID
P06047
Time
3:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4023
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
WO_602600_TV05009_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0817
Downstream MH
05 0816
Dir. of Survey
Downstream
Length Surveyed
336.4 ft.
Total Length
336.4 ft.
Structural Index
3
Structural Quick
3L21
Structural Rating
200
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
336
Pipe schematic from manhole 05 0817 to 05 0816
MH: 05 0817MH: 05 0816downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08170 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"131.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: NO230.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS329.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish334.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0816

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: NO

    227.9 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    327.1 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

Observations (23)

DistanceCodeObservation
31.2TFC
128.3TFC
334.7DAGS
334.7CM
180.8TF
178.1TFA
230.6TF
0AMH05 0817
28.7TFC
277.6TFA
227.9TF
131.5TF
2DAGS
78.5TFC
336.4AMH05 0816
280.1TFA
0MWM
327.1TFDROOTS
0MWL
81.1TFC
329.9TFA
227.9CS
5CM

Properties (6)

additional_info
SC306415
custom_field_two
3
customer
LACSD
datetime
2016-11-29T03:12:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false