Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2016, 06:58 AM
  • H 1485_H 1484 _12122016_231847.mp4

Date
12/12/2016
W/O
602238
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01206
PipeID
P16445
Time
10:58 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3937
Sewer Name
H JOINT OUTFALL H - UNIT 8M RELIEF
City
WEST COVINA, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_602238_TV22148_NOV2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
H 1485
Downstream MH
H 1484
Dir. of Survey
Downstream
Length Surveyed
775.2 ft.
Total Length
775.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 1485 to H 1484
MH: H 1485MH: H 1484downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14850 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG.H.C. START2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start771 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish775.2 ft. AMH - Downstream Manhole, Survey Ends - H 1484

Observation photos (2)

  • General Observation - MAG.H.C. START

    2 ft. - General Observation - MAG.H.C. START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2MGOMAG.H.C. START
771SAV
775.2AMHH 1484
0MWL
2SAV
0AMHH 1485
0MWM

Properties (6)

additional_info
SC317681
custom_field_two
3
customer
LACSD
datetime
2016-12-12T22:58:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false