Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2016, 07:03 AM
  • E 0065_E 0064_29092016_000331.mp4

Date
09/29/2016
W/O
592161
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00030
PipeID
P11295
Time
12:03 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3594
Sewer Name
E JOINT OUTFALL E - UNIT 4
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_592161_TV01079_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
E 0065
Downstream MH
E 0064
Dir. of Survey
Downstream
Length Surveyed
336.9 ft.
Total Length
336.9 ft.
Structural Index
3
Structural Quick
523K
Structural Rating
190
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole E 0065 to E 0064
MH: E 0065MH: E 0064downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00650 ft. MWL - Water Level, 35 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start2.1 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO7.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish37.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start150.1 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO332.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish336.9 ft. AMH - Downstream Manhole, Survey Ends - E 0064

Observation photos (4)

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

    2.1 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    37.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    150.1 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
336.9AMHE 0064
2.1SRV
2.1SAP
0MWM
0AMHE 0065
37.9SAV
332.4SAV
150.1SRV
0MWL
7.6SRV

Properties (6)

additional_info
SC306189
custom_field_two
2
customer
LACSD
datetime
2016-09-29T00:03:13-07:00
documentation
PROPIPE
is_lateral_inspection
false