Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2016, 10:02 AM
  • 01 0663_01 0662_29092016_030245.mp4

Date
09/29/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01371
Time
3:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3595
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
01 0663
Downstream MH
01 0662
Dir. of Survey
Downstream
Length Surveyed
495.8 ft.
Total Length
495.8 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0663 to 01 0662
MH: 01 0663MH: 01 0662downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06630 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 70%118.1 ft. SAV - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO124 ft. SAV - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO422 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"430.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"462.4 ft. SAP - Surface Aggregate Projecting, from 11 to 12 o'clock, within 8 inches of joint: NO495.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0662

Observation photos (3)

  • Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

    118.1 ft. - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

    124 ft. - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 11 to 12 o'clock, within 8 inches of joint: NO

    462.4 ft. - Surface Aggregate Projecting, from 11 to 12 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
422TF
118.1SAV
0AMH01 0663
0MWL
2MGOMAG COAT 70%
430.6TF
124SAV
462.4SAP
0MWM
495.8AMH01 0662

Properties (6)

additional_info
SC306190
custom_field_two
3
customer
LACSD
datetime
2016-09-29T03:02:14-07:00
documentation
PROPIPE
is_lateral_inspection
false