Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2016, 08:42 AM
  • 01 0689_01 0688_03102016_014300.mp4

Date
10/03/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01398
Time
1:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3597
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0689
Downstream MH
01 0688
Dir. of Survey
Downstream
Length Surveyed
278.8 ft.
Total Length
278.8 ft.
Structural Index
3
Structural Quick
513J
Structural Rating
167
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
167
Pipe schematic from manhole 01 0689 to 01 0688
MH: 01 0689MH: 01 0688downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06890 ft. MWM - Water Mark, 20 %of cross sectional area3.3 ft. MGO - General Observation - MAG COAT 60%6.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start268.5 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO274.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish278.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0688

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    6.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

    268.5 ft. - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
6.4SAP
0MWL
3.3MGOMAG COAT 60%
0AMH01 0689
268.5SRV
274.1SAP
0MWM
278.8AMH01 0688

Properties (6)

additional_info
SC306192
custom_field_two
3
customer
LACSD
datetime
2016-10-03T01:42:16-07:00
documentation
PROPIPE
is_lateral_inspection
false