Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2016, 09:21 AM
  • 01 0664_01 0663_29092016_022159.mp4

Date
09/29/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01372
Time
2:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3595
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
01 0664
Downstream MH
01 0663
Dir. of Survey
Downstream
Length Surveyed
413 ft.
Total Length
413 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0664 to 01 0663
MH: 01 0664MH: 01 0663downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06640 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT 80%15.5 ft. SAV - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO66.1 ft. SAP - Surface Aggregate Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO413 ft. AMH - Downstream Manhole, Survey Ends - 01 0663

Observation photos (2)

  • Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

    15.5 ft. - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO

    66.1 ft. - Surface Aggregate Projecting, from 01 to 02 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
0AMH01 0664
0MGOCONNECTION AT MH 3 O'CLOCK
2.1MGOMAG COAT 80%
413AMH01 0663
15.5SAV
0MWL
66.1SAP
0MWM

Properties (6)

additional_info
SC306190
custom_field_two
3
customer
LACSD
datetime
2016-09-29T02:21:49-07:00
documentation
PROPIPE
is_lateral_inspection
false