Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2016, 05:45 AM
  • 01 0679_01 0678_03102016_224812.mp4

Date
10/03/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01388
Time
10:45 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3598
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0679
Downstream MH
01 0678
Dir. of Survey
Downstream
Length Surveyed
348.3 ft.
Total Length
348.3 ft.
Structural Index
5
Structural Quick
5E32
Structural Rating
151
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
151
Pipe schematic from manhole 01 0679 to 01 0678
MH: 01 0679MH: 01 0678downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06790 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. MGO - General Observation - MAG COAT 70%3.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start56.8 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO60.3 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO62.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start124.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"167.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"171.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish224.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"248.8 ft. SRV - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO252.4 ft. SRV - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO300.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO308.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start346.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Finish346.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish348.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0678

Observation photos (8)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    56.8 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    60.3 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    62.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO

    248.8 ft. - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO

    252.4 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    300.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start

    308.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start

Observations (20)

DistanceCodeObservation
62.3SRV
0MWM
171.1SRV
0MWL
60.3SRV
0AMH01 0679
300.8SRV
124.1TFA
346.6SRV
2MGOMAG COAT 70%
56.8SRV
308.2SRV
346.6SAP
167.2TF
3.7SAP
348.3AMH01 0678
224.8TF
252.4SRV
0MGOCONNECTION AT MH 9 O'CLOCK
248.8SRV

Properties (6)

additional_info
SC306193
custom_field_two
2
customer
LACSD
datetime
2016-10-03T22:45:59-07:00
documentation
PROPIPE
is_lateral_inspection
false