Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2020, 11:46 AM
  • J 0060_J 0059_1312020_044349.mp4

Date
01/31/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P11638
Time
3:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1344
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
LOMITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20200131MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0060
Downstream MH
J 0059
Dir. of Survey
Downstream
Length Surveyed
622.2 ft.
Total Length
622.2 ft.
Structural Index
3
Structural Quick
4135
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
25
Pipe schematic from manhole J 0060 to J 0059
MH: J 0060MH: J 0059downstream0 ft. MGO - General Observation - 95% MAG COAT START0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE30.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE112.3 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG134.1 ft. SAV - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG168.5 ft. SSS - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE241.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG431.5 ft. SAV - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVCERE AGG592 ft. SAM - Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT622.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG622.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE622.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active622.2 ft. SAM - Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG622.2 ft. MGO - General Observation - MAG COAT 95% FINISH

Observation photos (10)

  • General Observation - 95% MAG COAT START

    0 ft. - General Observation - 95% MAG COAT START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

    30.4 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    112.3 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    134.1 ft. - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    168.5 ft. - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    241.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVCERE AGG

    431.5 ft. - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVCERE AGG

  • Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    592 ft. - Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

Observations (18)

DistanceCodeObservation
0MGO95% MAG COAT START
2SAVSEVERE AGG SPORATIC
2SSSBLISTERING FLAKING CONCRETE
0AMH4:35AM
622.2SAVSEVERE AGG
0MWL
622.2SSSBLISTERING FLAKING CONCRETE
622.2MGOConn. @ Mh, 9 O' Clock. Active
0MWM
241.5SAVSEVERE AGG
431.5SAVSEVCERE AGG
622.2SAMSEVERE AGG
30.4SSSBLISTERING FLAKING CONCRETE
112.3SAVSEVERE AGG
592SAMSEVERE AGG UNDER MAG COAT
622.2MGOMAG COAT 95% FINISH
134.1SAVSEVERE AGG
168.5SSSBLISTERING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG MISSING-95% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2020-01-31T03:46:30-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false