Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2020, 10:26 AM
  • J 0062_J 0061_1312020_024600.mp4

Date
01/31/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P11640
Time
2:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1344
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
LOMITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20200131MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0062
Downstream MH
J 0061
Dir. of Survey
Downstream
Length Surveyed
940.8 ft.
Total Length
940.8 ft.
Structural Index
3
Structural Quick
3625
Structural Rating
28
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
28
Pipe schematic from manhole J 0062 to J 0061
MH: J 0062MH: J 0061downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE2 ft. MGO - General Observation - 95% MAG COAT START2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC27.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, - BLISTERING FLAKING CONCRETE124.8 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG239.5 ft. SAV - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC249.4 ft. SAV - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG298.1 ft. MGO - General Observation - MAG COAT 90% START298.1 ft. SAV - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC457.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active564.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE662.7 ft. MGO - General Observation - 98% MAG COAT830.8 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVEWRE AGGT940.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC940.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE940.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE940.3 ft. MGO - General Observation - MAG COAT 90% FINISH940.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish940.8 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (11)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • General Observation - 95% MAG COAT START

    2 ft. - General Observation - 95% MAG COAT START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO,  - BLISTERING FLAKING CONCRETE

    27.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    124.8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    239.5 ft. - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    249.4 ft. - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    298.1 ft. - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    564.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • General Observation - 98% MAG COAT

    662.7 ft. - General Observation - 98% MAG COAT

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVEWRE AGGT

    830.8 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVEWRE AGGT

Observations (22)

DistanceCodeObservation
249.4SAVSEVERE AGG
662.7MGO98% MAG COAT
0AMH2:45AM
2SSSBLISTERING FLAKING CONCRETE
0MWL
940.8AMH3:40AM
457.6TFAActive
940.3SSSSEVERE AGG SPORATIC
940.3SSSBLISTERING FLAKING CONCRETE
564.6SSSBLISTERING CONCRETE
298.1MGOMAG COAT 90% START
830.8SAVSEVEWRE AGGT
2MGO95% MAG COAT START
940.3SSSBLISTERING CONCRETE
0MWM
27.2SSSBLISTERING FLAKING CONCRETE
940.3MGOMAG COAT 90% FINISH
239.5SAVSEVERE AGG SPORATIC
298.1SAVSEVERE AGG SPORATIC
2SAVSEVERE AGG SPORATIC
940.3SSS
124.8SAVSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG VISIBLE - 90% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2020-01-31T02:26:39-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false