Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2018, 08:29 AM
  • 22 0244_22 0243 _11012018_002956.mp4

Date
01/11/2018
W/O
679679
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16526
Time
12:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5410
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_679679_TV22160_JAN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0243
Downstream MH
22 0244
Dir. of Survey
Upstream
Length Surveyed
106.9 ft.
Total Length
107 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
105
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
105
Pipe schematic from manhole 22 0243 to 22 0244
MH: 22 0243MH: 22 0244upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 02440 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"56.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start104.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start107 ft. MWM - Water Mark, 25 %of cross sectional area107 ft. AMH - Downstream Manhole, Survey Begins - 22 0243107 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2.1SSS
50.3TFC
107AMH22 0244
0MWM
106.6TFC
0AMH22 0243
107SAP
46.9TFC
107MGOCONNECTION AT MH 3 O'CLOCK
107SSS
0MWL
2.1SAP

Properties (6)

additional_info
SC346784
custom_field_two
2
customer
LACSD
datetime
2018-01-11T00:29:12-08:00
documentation
PROPIPE
is_lateral_inspection
false