Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2018, 09:23 AM
  • 22 0234_22 0320 _12012018_012410.mp4

Date
01/12/2018
W/O
679679
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16516
Time
1:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5413
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_679679_TV22160_JAN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0234
Downstream MH
22 0320
Dir. of Survey
Downstream
Length Surveyed
402.5 ft.
Total Length
402.6 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
243
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
243
Pipe schematic from manhole 22 0234 to 22 0320
MH: 22 0234MH: 22 0320downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02340 ft. MWM - Water Mark, 30 %of cross sectional area3.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"37 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"83.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"181 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.7 ft. CM - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES276.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"279 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"330.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"380 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"383 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"402.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0320402.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    243.7 ft. - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
0MWL
279TFC
276.1TFC
380TFC
3.2SAP
37TFC
327.9TFC
402.6SAP
330.8TFC
383TFC
135.1TFC
183.9TFC
243.7CM
402.6AMH22 0320
132.1TFC
86.3TFC
402.6MGOCONNECTION AT MH 3 O'CLOCK
34.3TF
330.8TF
0AMH22 0234
230.1TF
181TF
83.1TF
0MWM
232.9TFC

Properties (6)

additional_info
SC346787
custom_field_two
3
customer
LACSD
datetime
2018-01-12T01:23:45-08:00
documentation
PROPIPE
is_lateral_inspection
false