Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2018, 10:04 AM
  • 22 0298_22 0297_08012018_020503.mp4

Date
01/08/2018
W/O
679260
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16584
Time
2:04 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5406
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
WO_679260_TV22014_JAN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0297
Downstream MH
22 0298
Dir. of Survey
Upstream
Length Surveyed
432.7 ft.
Total Length
432.7 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
425
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
425
Pipe schematic from manhole 22 0297 to 22 0298
MH: 22 0297MH: 22 0298upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 02981.5 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish2.3 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish43.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"124 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"329.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"361.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"393.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"423.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"428.8 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start428.8 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start432.7 ft. AMH - Downstream Manhole, Survey Begins - 22 0297432.7 ft. MWM - Water Mark, 15 %of cross sectional area432.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
39.1TFC
308.7TFC
431.2SSS
9.6TF
432.7AMH22 0298
430.4SAP
103.1TFC
0AMH22 0297
233.3TF
160.1TF
71.6TF
253.1TF
385TF
0MWM
389.2TFC
304.5TF
0MWL
3.9SSS
123.2TF
193.8TF
3.9SAP

Properties (6)

additional_info
SC346780
custom_field_two
2
customer
LACSD
datetime
2018-01-08T02:04:35-08:00
documentation
PROPIPE
is_lateral_inspection
false