Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2018, 07:51 PM
  • A 0420_A 0419_16012018_122707.mp4

Date
01/16/2018
W/O
668747
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00322
PipeID
P08080
Time
11:51 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5173
Sewer Name
A JOA-1A LONG BEACH WRP SLUDGE GRAVITY SEWER
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
11
Purpose
Routine Assessment
Project
WO_668747_TV19010_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
A 0420
Downstream MH
A 0419
Dir. of Survey
Downstream
Length Surveyed
354.1 ft.
Total Length
354.1 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
140
O&M Index
2
O&M Quick
423I
O&M Rating
331
Overall Index
2
Overall Quick
Overall Rating
471
Pipe schematic from manhole A 0420 to A 0419
MH: A 0420MH: A 0419downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 04200 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MWM - Water Mark, 70 %of cross sectional area1.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - SLUDGE29.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start85.5 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR90.2 ft. RMJ - Roots Medium Joint, from 12 to 04 o'clock, 15 %, within 8 inches of joint: YESR102.6 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR105.4 ft. RBJ - Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YES109.9 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 40 %, within 8 inches of joint: YESR117 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Start133.7 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start145.9 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Finish149.9 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 20 %, within 8 inches of joint: YESR224.3 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE352.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish352.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish352.7 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish354.1 ft. AMH - Downstream Manhole, Survey Ends - A 0419

Observation photos (11)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    1.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    29.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR

    85.5 ft. - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR

  • Roots Medium Joint, from 12 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    90.2 ft. - Roots Medium Joint, from 12 to 04 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR

    102.6 ft. - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR

  • Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YES

    105.4 ft. - Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YES

  • Roots Medium Joint, from 09 to 03 o'clock, 40 %, within 8 inches of joint: YESR

    109.9 ft. - Roots Medium Joint, from 09 to 03 o'clock, 40 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    117 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start

    133.7 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Finish

    145.9 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Finish

  • Roots Medium Joint, from 09 to 03 o'clock, 20 %, within 8 inches of joint: YESR

    149.9 ft. - Roots Medium Joint, from 09 to 03 o'clock, 20 %, within 8 inches of joint: YESR

Observations (20)

DistanceCodeObservation
85.5RFJ
352.7SSS
105.4RBJ
90.2RMJ
117RFJ
352.7DAE
0AMHA 0420
224.3DSZSLUDGE
109.9RMJ
0MWL
0MWM
102.6RFJ
149.9RMJ
133.7RMJ
352.7RFJ
1.5SSS
354.1AMHA 0419
29.7DAE
7DSZSLUDGE
145.9RMJ

Properties (6)

additional_info
SC347003
custom_field_two
3
customer
LACSD
datetime
2018-01-16T11:51:38-08:00
documentation
PROPIPE
is_lateral_inspection
false