Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2018, 04:57 PM
  • Section#1_15 0438_15 0437__1292018__G6738.mp4

Date
01/29/2018
W/O
0630292
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00625
PipeID
P12364
Time
8:57 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6738
Sewer Name
15 RIVER AVENUE TRUNK
City
ROSEMEAD
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
20180129DF_RIVER_AVE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0438
Downstream MH
15 0437
Dir. of Survey
Downstream
Length Surveyed
420.5 ft.
Total Length
420.5 ft.
Structural Index
2
Structural Quick
4131
Structural Rating
128
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
128
Pipe schematic from manhole 15 0438 to 15 0437
MH: 15 0438MH: 15 0437downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:45 AM0.1 ft. MWM - Water Mark, 25 %of cross sectional area11.3 ft. JOM - Joint Offset Medium - .526.9 ft. B - Broken, from 07 to 08 o'clock, within 8 inches of joint: YES127.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start132 ft. MGP - General Photograph213.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES248.7 ft. MGP - General Photograph299.2 ft. CM - Crack Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES418.3 ft. CS - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES418.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish420.5 ft. AMH - Downstream Manhole, Survey Ends - 11:07 AM

Observation photos (8)

  • Joint Offset Medium - .5

    11.3 ft. - Joint Offset Medium - .5

  • Broken, from 07 to 08 o'clock, within 8 inches of joint: YES

    26.9 ft. - Broken, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    127.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    132 ft. - General Photograph

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    213.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • General Photograph

    248.7 ft. - General Photograph

  • Crack Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES

    299.2 ft. - Crack Multiple, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

    418.3 ft. - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
213.2CL
11.3JOM.5
0.1MWM
26.9B
299.2CM
418.3CS
248.7MGP
0MWL
132MGP
0AMH9:45 AM
420.5AMH11:07 AM
418.3SSS
127.2SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2018-01-29T08:57:01-08:00
documentation
FRANKLIN, IGNACIO, VENDRYES
is_lateral_inspection
false