Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2017, 07:14 AM
  • 02 0221_02 0220A_7182017_010637.mp4

Date
07/18/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
Reveles
Sewer ID
Z00251
PipeID
P26544
Time
12:14 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0593
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20170714VMR_DOWNEY_BELLFOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0221
Downstream MH
02 0220A
Dir. of Survey
Downstream
Length Surveyed
360.2 ft.
Total Length
360.2 ft.
Structural Index
2
Structural Quick
352A
Structural Rating
41
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 02 0221 to 02 0220A
MH: 02 0221MH: 02 0220Adownstream0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 8" - Active0 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 8" - Active0 ft. AMH - Upstream Manhole, Survey Begins - 01:10 am0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area6.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES11.1 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES, Start14.7 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish14.9 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES19.2 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES27.4 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES35.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES39.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES43.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES52 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES52 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES56.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES60.4 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES72.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES80.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES89.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES89.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES90.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open93.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8" - Open99.4 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES103.5 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES111.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES119.7 ft. CC - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES199.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"202.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"287.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"290.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"302.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Active357.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES - Throughout the reach357.3 ft. MGO - General Observation - Cracks throughout the reach357.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES - Throughout the reach360.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 8"360.2 ft. AMH - Downstream Manhole, Survey Ends - 2:46 am

Observation photos (2)

  • Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Active

    302.8 ft. - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Active

  • Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    360.2 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 8"

Observations (38)

DistanceCodeObservation
35.5CL
27.4CM
0TFAActive
357.3DAGSThroughout the reach
6.5CM
60.4CM
14.7CM
202.3TFC
360.2TF
52CL
43.9CL
0TFAActive
357.3MGOCracks throughout the reach
19.2CC
89.9CL
199.3TFC
0AMH01:10 am
357.3DAGSThroughout the reach
103.5CC
72.8CL
80.8CL
39.6CL
90.5TFOpen
99.4CM
0MWM
0MWL
290.1TFC
360.2AMH2:46 am
302.8TFAActive
89.9CL
287.8TFC
93.9TFOpen
11.1CM
14.9CC
119.7CC
111.8CL
56.2CL
52CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-07-18T00:14:57-07:00
documentation
REVELES, MANANES, OLIVER
is_lateral_inspection
false