Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2017, 11:00 AM
  • B 0627_B 0626_532017_041624.mp4

Date
05/03/2017
W/O
0624373
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00107
PipeID
P09292
Time
4:00 AM
Certificate
U-1-14-06O22543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0514
Sewer Name
B JOINT OUTFALL B - UNIT 8D
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
20170503MDM_JOINT_OUTFALL_B_UNIT_8D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
B 0627
Downstream MH
B 0626
Dir. of Survey
Downstream
Length Surveyed
282.7 ft.
Total Length
282.7 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole B 0627 to B 0626
MH: B 0627MH: B 0626downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN,FLAKING CONCRETE2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:0089.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE198.9 ft. MGO - General Observation - 1214.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE241.8 ft. SAV - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - 3 SEVERE AGGS259.5 ft. SSS - Surface Spalling, from 09 to 10 o'clock, within 8 inches of joint: NO - PEELING LAITANCE COAT282.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN,FLAKING CONCRETE282.1 ft. MGO - General Observation - MAG COAT 80% FINISH282.7 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (7)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN,FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN,FLAKING CONCRETE

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE

    89.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE

  • General Observation - 1

    198.9 ft. - General Observation - 1

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE

    214.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN,FLAKING CONCRETE

  • Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - 3 SEVERE AGGS

    241.8 ft. - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - 3 SEVERE AGGS

  • Surface Spalling, from 09 to 10 o'clock, within 8 inches of joint: NO - PEELING LAITANCE COAT

    259.5 ft. - Surface Spalling, from 09 to 10 o'clock, within 8 inches of joint: NO - PEELING LAITANCE COAT

Observations (14)

DistanceCodeObservation
0MWL
214.1SSSSWOLLEN,FLAKING CONCRETE
241.8SAV3 SEVERE AGGS
89.8SSSSWOLLEN,FLAKING CONCRETE
282.1SSSSWOLLEN,FLAKING CONCRETE
282.7AMH4:45AM
0AMH4:15AM
2SSSSWOLLEN,FLAKING CONCRETE
282.1MGOMAG COAT 80% FINISH
2MGOMAG COAT 80% START 9:00 TO 3:00
259.5SSSPEELING LAITANCE COAT
0MWM
198.9MGO1
0MGOConn. @ Mh, 3 O' Clock. STUB

Properties (6)

custom_field_three
SPALLING CONCRETE
custom_field_two
4
customer
LACSD
datetime
2017-05-03T04:00:18-07:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false