Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2017, 07:29 PM
  • 05 1125_05 1124_512017_123335.mp4

Date
05/01/2017
W/O
0630075
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00489
PipeID
P06361
Time
12:29 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7394
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 2
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
20170501DF_MONETA_EXTENSION_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1125
Downstream MH
05 1124
Dir. of Survey
Downstream
Length Surveyed
257.1 ft.
Total Length
257.1 ft.
Structural Index
3
Structural Quick
5341
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 05 1125 to 05 1124
MH: 05 1125MH: 05 1124downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:31 PM0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.9 ft. MGO - General Observation - ROACHES @ MH6 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES6 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES7.4 ft. MGO - General Observation - CHIPPING FROM 12 TO 12 O'CLOCK @ JOINT15.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES42.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open46.2 ft. B - Broken, from 09 to 04 o'clock, within 8 inches of joint: YES92.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open96.6 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES141.4 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES143.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open146.7 ft. CM - Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES150.8 ft. CM - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES193.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4"246 ft. B - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES247.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open251 ft. B - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES253.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish257.1 ft. AMH - Downstream Manhole, Survey Ends - 1:06 PM257.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN

Observation photos (12)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

    6 ft. - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    6 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - CHIPPING FROM 12 TO 12 O'CLOCK @ JOINT

    7.4 ft. - General Observation - CHIPPING FROM 12 TO 12 O'CLOCK @ JOINT

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    15.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 04 o'clock, within 8 inches of joint: YES

    46.2 ft. - Broken, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    96.6 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    141.4 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    146.7 ft. - Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

    150.8 ft. - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

    246 ft. - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

    251 ft. - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
15.9CL
7.4MGOCHIPPING FROM 12 TO 12 O'CLOCK @ JOINT
143.2TFOpen
0AMH12:31 PM
6B
253.8CM
251B
150.8CM
257.1AMH1:06 PM
141.4CM
6CM
246B
0.2MGOConn. @ Mh, 3 O' Clock. Active
46.2B
247.7TFOpen
193.5TFA
92.6TFOpen
257.1MGOConn. @ Mh, 9 O' Clock. OPEN
2CM
253.8SSS
0MWL
2SSS
2.9MGOROACHES @ MH
146.7CM
96.6CM
0MWM
42.8TFOpen

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-05-01T12:29:06-07:00
documentation
FRANKLIN, IGNACIO
is_lateral_inspection
false