Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2017, 03:42 PM
  • 05 1130_05 1129_4282017_093622.mp4

Date
04/28/2017
W/O
0630075
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00489
PipeID
P06366
Time
8:42 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7391
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 2
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
20170427MI_MONETA_EXTENSION_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1130
Downstream MH
05 1129
Dir. of Survey
Downstream
Length Surveyed
335.3 ft.
Total Length
335.3 ft.
Structural Index
3
Structural Quick
4336
Structural Rating
32
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 05 1130 to 05 1129
MH: 05 1130MH: 05 1129downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 09:33 AM4.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES39 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES48.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"54.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.1 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES104.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6" - Open161 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open172.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES201.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES206.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Active259.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open275.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES303.5 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES305.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open309 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES311.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"314 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES334.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335.3 ft. AMH - Downstream Manhole, Survey Ends - 10:06 AM

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    39 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    48.7 ft. - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    102.1 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    172.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    275.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Downstream Manhole, Survey Ends - 10:06 AM

    335.3 ft. - Downstream Manhole, Survey Ends - 10:06 AM

Observations (27)

DistanceCodeObservation
109.4TFA
335.3AMH10:06 AM
54.1TFA
334.4SSS
212.1TFC
155.6TFOpen
5.8CM
201.9CM
48.7TFA
0MWL
275.3FM
254.1TFActive
4.2SSS
172.2FM
104.2TFA
305.7TFOpen
309CM
311.3TFA
39FM
0MWM
303.5CM
102.1CM
0AMH09:33 AM
206.7TFC
314CM
161TFOpen
259.9TFOpen

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-04-28T08:42:07-07:00
documentation
IGNACIO, FRANKLIN
is_lateral_inspection