30 0281_30 0280_4272017_103612.mp4
0 ft. - General Observation - FINE ROOTS AT THE MH
4.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
4.6 ft. - Roots Fine Joint, from 04 to 08 o'clock, within 8 inches of joint: YESR, Start
57.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES
69.7 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - BLOCKED WITH DEBRIS, 50%
116.8 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - BLOCKED WITH ROOTS, 90%
138 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES
144 ft. - General Observation - DROP CONNECTION AT MH, 12 OCLOCK
144 ft. - Downstream Manhole, Survey Ends - 11:00 AM
| Distance | Code | Observation |
|---|---|---|
| 4.6 | RFJ | — |
| 7.9 | CM | — |
| 138 | B | — |
| 0 | MWL | — |
| 116.8 | TFD | BLOCKED WITH ROOTS, 90% |
| 4.1 | SSS | — |
| 142.5 | SSS | — |
| 144 | MGO | DROP CONNECTION AT MH, 12 OCLOCK |
| 0 | AMH | 10:35 AM |
| 17.7 | CM | — |
| 57.6 | DAE | — |
| 0 | MGO | FINE ROOTS AT THE MH |
| 0 | MWM | — |
| 69.7 | TFD | BLOCKED WITH DEBRIS, 50% |
| 142.5 | RFJ | — |
| 144 | AMH | 11:00 AM |